Calcium Phosphate Scale Formation in Power Station Condensers Fed by Cooling Towers: A Case of When Not to Use Scaling Indices
View / Open Files
Authors
Hawthorn, Donald
Wilson, D Ian
Publication Date
2020Journal Title
HEAT TRANSFER ENGINEERING
ISSN
0145-7632
Publisher
Informa UK Limited
Volume
41
Issue
2
Pages
138-148
Type
Article
This Version
AM
Metadata
Show full item recordCitation
Hawthorn, D., & Wilson, D. I. (2020). Calcium Phosphate Scale Formation in Power Station Condensers Fed by Cooling Towers: A Case of When Not to Use Scaling Indices. HEAT TRANSFER ENGINEERING, 41 (2), 138-148. https://doi.org/10.1080/01457632.2018.1522082
Abstract
Unexpected fouling in condensers on Central Electricity Generating Board power stations operating on the river Trent in the UK in the 1970s prompted an extensive investigation of the phenomenon. Fouling was caused by deposition of calcium phosphate rich scale on the cooling water side. A fouling test rig was specially constructed to study the performance of different chemical treatments. The rig ran two tubes in parallel, one with un-dosed water, and the latter’s data sets from over 100 ‘control’ tests were analysed to determine the mechanism and rate of fouling. The trends could not be explained in terms of conventional scaling indices. Insight into the mechanism was provided by separating precipitation (loss from solution) and deposition (adhesion of some of the precipitated mass to the heated surface): scaling was found to be caused by the deposition of particulates in the recirculating cooling water, driven by the change in pH as the water went through the evaporative cooling stage. Quantitative expressions for fouling were generated from tests on 1.83 m long tubes and were found to give a reasonable prediction of the fouling behaviour observed on a full sized (18.3 m long) single condenser tube on an operating condenser. The results indicated that recirculating water systems need to be approached very differently to once-through systems, and the use of scaling indices for such systems is not recommended.
Identifiers
External DOI: https://doi.org/10.1080/01457632.2018.1522082
This record's URL: https://www.repository.cam.ac.uk/handle/1810/287840
Rights
Licence:
http://www.rioxx.net/licenses/all-rights-reserved
Statistics
Total file downloads (since January 2020). For more information on metrics see the
IRUS guide.
Recommended or similar items
The current recommendation prototype on the Apollo Repository will be turned off on 03 February 2023. Although the pilot has been fruitful for both parties, the service provider IKVA is focusing on horizon scanning products and so the recommender service can no longer be supported. We recognise the importance of recommender services in supporting research discovery and are evaluating offerings from other service providers. If you would like to offer feedback on this decision please contact us on: support@repository.cam.ac.uk